Under-Slab Insulation and Vapor Barrier
Insulation under a concrete slab is only required by code around the perimeter: R-10, 2 to 4 feet deep, in climate zones 3 to 8 under the 2021 IECC. Insulation under the whole floor is required only for a heated slab, at R-5. The vapor retarder goes directly under the concrete, on top of any foam, and should carry an ASTM E1745 class rather than just a mil thickness.
Does code require insulation under a slab?
No, only at the edge. The 2021 IECC covers slab-on-grade floors less than 12 inches below grade (PNNL code brief) and sets an edge R-value and depth by climate zone (PNNL table). An unheated slab needs nothing under the middle.
R-value and depth by climate zone and code edition
| Climate zone | 2009 to 2018 | 2021 |
|---|---|---|
| 0 to 2 | None | None |
| 3 | None | R-10, 2 ft |
| 4 and 5 | R-10, 2 ft | R-10, 4 ft |
| 6 to 8 | R-10, 4 ft | R-10, 4 ft |
The table covers floors less than 12 inches below grade, so a basement floor is a separate case. Check which edition your town has adopted, since the depths changed in 2021.
Heated slabs need R-5 under the whole floor
A heated slab gets R-5 under its full area on top of the edge value, and its edge insulation no longer has to run below the slab. R-5 is about 1 inch of XPS. The rest of that system is in heated concrete floors.
It counts as heated
Within or under
Heating in contact with, within or under the slab, per the IECC definition.
Washington
R-10
Under the full area of a heated slab, on every compliance path (WAC 51-11R).
Termite areas restrict foam below grade. Where termite risk is "very heavy", IRC R318.4 says foam plastics "shall not be installed on the exterior face or under interior or exterior foundation walls or slab foundations located below grade" (South Carolina's adopted text). Ask the building official how your area handles that alongside the energy code.
Does the insulation go above or below the vapor barrier?
Below. The order is subgrade, granular base, foam, vapor retarder, then concrete, with the sheet touching the slab. ACI 302.1R-15 says direct contact with the slab gives "the greatest level of protection" for floor coverings, and Building Science Corporation warns not to put the plastic under the foam "as it will keep the insulation wet."
- Lay 4 inches of clean base. IRC R506.2.2 calls for a 4 inch base of clean graded sand, gravel or crushed stone under slabs below grade, unless the soil is well drained. Foam doesn't replace it, and foam on a soft subgrade telegraphs every low spot.
- Set the foam tight. Butt the boards and run the edge insulation to the depth your zone needs.
- Roll the retarder over the foam. Lap seams at least 6 inches, or 12 inches where the sheet is also the radon retarder under IRC Appendix F (AF103.3).
- Patch every tear before the pour. Rebar chairs and boots puncture it; tape any hole the inspection finds.
- Pour straight onto the sheet. No sand layer on top of it.
Advice online splits because ACI changed its mind: its 1996 guide favored a layer of fill between the sheet and the slab so the slab could dry down, then flooring failures on those jobs moved it to direct contact in the 2004 edition, kept in 302.1R-15. NRMCA's CIP 29 still allows a dry granular layer of at least 4 inches over the sheet, but only where no moisture-sensitive flooring is planned, and never concrete sand. More on slab build-up is in concrete floor thickness.
6 mil or 10 mil vapor barrier?
Neither thickness is the real spec. ACI 302.1R-15 says ordinary 6, 8 and 10 mil polyethylene "does not fully conform to the requirements of ASTM E1745" and shouldn't be used as below-slab moisture protection. Buy a sheet that states an ASTM E1745 class.
Class A
2,200 g
Puncture resistance; tensile 45 lbf/in.
Class B
1,700 g
Puncture resistance; tensile 30 lbf/in.
Class C
475 g
Puncture resistance; tensile 13.6 lbf/in.
All three classes have the same 0.1 perm limit, and ASTM E1745 sets no thickness at all, so the class is a toughness rating for a sheet that gets walked on and loaded with rebar chairs.
What the IRC requires, by edition
2015 and 2018
6 mil
Polyethylene or an approved retarder.
2021
10 mil
Meeting ASTM E1745 Class A (R506.2.3).
2024
6 mil
Polyethylene allowed again, per NAHB.
Most outbuildings and flatwork need no retarder. The IRC exempts garages, utility buildings and other unheated accessory structures, unheated storage rooms under 70 sq ft, carports, and "driveways, walks, patios and other flatwork not likely to be enclosed and heated at a later date" (2018 IRC as adopted).
Is it worth insulating if code doesn't require it?
Under a heated slab, yes. Under an unheated slab, edge insulation on a new build is the code minimum and the edge is where heat goes; full-area foam is a comfort choice. Retrofitting edge foam onto an existing home pays back slowly.
Edges lose the most
20%+
Slab edges and corners swung 1.6 to 2.1 times more in temperature than the core, and perimeter XPS cut ground-floor heat loss over 20 percent, in a full-scale Australian test.
Payback
18 to 47 years
For adding edge insulation to existing homes in zones 4 to 7, a DOE Building America study found site energy savings of 5 percent or less, "not cost-effective" on their own.
XPS, EPS or polyiso under a slab
All three can go under a slab; what matters is how much R-value survives years of wet ground. An Oak Ridge National Laboratory field study of 15-year-old exterior XPS found it had lost about 10 percent of its energy-saving performance on a basement and 44 percent at a slab edge, mostly from moisture.
EPS makers say
18.9% water
In a 15-year-old buried XPS sample, which kept about half its R-value, per an EPS Molders Association bulletin.
XPS makers say
R-4.1 vs R-2.2
DuPont cites Alaska samples: XPS about R-4.1 an inch after 31 years, EPS about R-2.2 after 21.
Each side sells the product it favors. Polyiso isn't banned below grade either: PIMA promotes it there, and Rmax Below Grade is rated ASTM C1289 Type I, 25 to 60 psi, for under-slab use.
Can you pour a concrete slab on foam?
Yes, by a wide margin: a house floor loads the foam far below even the softest grade.
50 psf slab + 40 psf live load = 90 psf
90 ÷ 144 = 0.625 psi on the foam
Type I EPS
10 psi
The softest grade.
Type IV XPS
25 psi
A common under-slab XPS.
Type VII XPS
60 psi
Point loads, lifts, racks.
Those ASTM C578 ratings are measured at yield or 10 percent deformation, not a safe working load; DuPont suggests a 3 to 1 safety factor for static loads, which still leaves 10 psi foam about 5 times the floor load and 25 psi foam about 13 times. Size the foam for the heaviest point load, such as a car lift anchor or rack foot, not the floor.
What under-slab insulation costs
Foam is the big line and the sheet costs cents. These are retail prices we checked in November 2026.
6 mil poly
$0.05 to $0.08
Per sq ft; doesn't meet E1745.
10 mil Class A
$0.16 to $0.31
Per sq ft, before laps.
1 in XPS, R-5
$0.65 to $0.90
Per sq ft, the heated slab minimum.
2 in XPS, R-10
$1.85 to $2.80
Per sq ft, the edge value.
That band takes about $830 to $1,250 of 2 inch XPS if it all runs flat under the slab; double both sides of the slab and the same band is only a quarter of the floor. Size the base with the gravel calculator and the concrete with the concrete floor calculator; how this layer compares with other floor budgets is in concrete floor cost.
What goes wrong
Most failures trace to the sheet: torn, buried under wet fill, or missing.
Flooring fails
Years on
Moisture through the slab breaks down adhesives, coatings and vinyl.
Curling
Top shrinks more
A slab that dries only upward curls at the edges.
Torn sheet
475 g
Class C puncture resistance, about a fifth of Class A.
Wet blotter
4 in of fill
ACI says fill between sheet and slab is "an avenue for moisture."
Frequently asked questions
Does code require insulation under a concrete slab?
Only at the edge for an unheated slab. The 2021 IECC asks for R-10 to 2 feet deep in climate zone 3 and 4 feet in zones 4 to 8, and nothing in zones 0 to 2. A heated slab also needs R-5 under its full area.
Does the insulation go above or below the vapor barrier?
Below. The order is base, foam, vapor retarder, then concrete, with the sheet touching the slab, which ACI 302.1R-15 says gives the greatest protection. Building Science Corporation warns that plastic under the foam keeps the insulation wet.
Is 6 mil or 10 mil plastic better under a slab?
Thickness is the wrong test: ACI says ordinary 6, 8 and 10 mil polyethylene does not fully conform to ASTM E1745. Buy a sheet with an E1745 class. The 2021 IRC required 10 mil Class A, and the 2024 IRC allows 6 mil polyethylene again, so check your adopted edition.
Can you pour a concrete slab on foam?
Yes. A 4 inch slab and a 40 psf live load put about 0.6 psi on the foam, and even with a 3 to 1 safety factor 25 psi foam has about 13 times that. Size the foam for point loads such as lift anchors or rack feet.
Does foam under a slab lose its R-value?
It can when it stays wet. An Oak Ridge National Laboratory study of 15-year-old exterior XPS found about 10 percent loss of energy-saving performance on a basement and 44 percent at a slab edge, mostly from moisture.
Do I still need gravel under the slab if there is insulation?
Usually. IRC R506.2.2 calls for a 4 inch base of clean sand, gravel or crushed stone under slabs below grade unless the soil is well drained, and foam needs that firm, even bed. Don't put a sand layer on top of the vapor retarder.